Technical parameters
|
Type |
Freeze liquefaction vacuum water cooling movable |
|
Operating temperature |
-10℃~40℃ |
|
Recovery |
Initial pressure (Mpa) |
0.8 |
|
Final pressure (Mpa) |
≤ 0.05 |
|
Time required for filling 1m3 volume of gas (h/m3) |
≤ 1 |
|
Filling gas |
Initial pressure (Pa) |
≤ 133 |
|
Initial pressure (Mpa) |
0.7 |
|
Time required for filling 1m3 volume of gas (h/m3) |
≤ 0.3 |
|
Time required for vacuum pumping from 0.1MPa to 133pa (h/m3) |
≤ 0.7 |
|
Limit vacuum (Pa) |
≤ 10 |
Purity of recovered SF6 gas
(50KG) |
Moisture (PPM/V) |
≤ 60 |
|
Oil fraction (PPM/W) |
≤ 5 |
|
Dust (um) |
≤ 1 |
|
Storage container |
Storage mode |
gas liquid |
|
Pressure (MPa) |
4.0 |
|
Volume (L) |
80 |
|
Liquid storage capacity (kg) |
80 |
|
Liquefaction method |
Freezing liquefaction |
|
Vaporization mode |
Electric heating |
|
Regeneration mode of drying filter |
Vacuum heating activation regeneration |
|
Power supply |
Three-phase 3Φ 380V with zero line |
|
Total power (kW) |
≤ 8 |
|
Noise dB(A) |
≤ 75 |
|
Dimension (mm) |
1400mm×1000mm×1000mm |
|
Weight (kg) |
≤ 680KG |
Main configuration
1. SF6 compressor requirements: CA-0300 hermetic compressor (COPELAND product from EMERSON USA)
a: Theoretical displacement: 12m3/h
b: Maximum exhaust pressure: 2.5Mpa
c: Minimum suction pressure: 50Kpa
d: Maximum suction pressure: 0.35~0.8 Mpa
e: Power: 2.2KW
f: Power supply: 380V 50HZ
2. Vacuum pump adopts: two-stage rotary vane vacuum pump (2XZ-4A)
a: The vacuum pump is water-cooled
b: Vacuum pumping rate 4L/s
c: Ultimate vacuum degree 0.06pa
d: Power 1KW
3. Requirement of SF6 refrigeration unit: Japan TOSHIBA joint venture host 1KW
4. Filtration system (purification system): filter two-stage filtration vacuum activation and self-regeneration processing)
5. Connector: M27*1.5
6. Safety valve: A21H
7. Valve: DN15—13.5MPa
8. Liquid storage tank: 80L maximum pressure 2.6Mpa
9. Pressure gauge: TECSIS Germany 1413 thermocouple vacuum gauge
10. Liquefier: heating