NRJF-3000 Digital partial discharge detector is a new generation of high-performance digital PD measurement and analysis instrument realized by a new technology, which is an alternative to the traditional analog PD instrument. Its unique anti-jamming technology allows you to make accurate measurements in high interference environments; User-friendly interface and high-speed sample refresh rate with visual effects of an analog PD instrument; A variety of waveform analysis and recording methods are provided to make it easy to judge the nature of the discharge; Automatic recording and processing of various test data, can quickly generate a test report with a good picture; Adopting dual-channel embedded system and TFT touch screen, the system is stable and reliable, and the failure rate is low; The system integrates computer technology, analog electronic technology, high-speed signal acquisition technology and advanced digital signal processing and graphic display technology to complete the automatic measurement and analysis of partial discharge.
Overview
● It can perform digital window opening operation open window at any phase single window double window optional and 360° rotation of ellipse to avoid the influence of interference on measurement.
● Multi-channel measurement and digital differential technology can flexibly form a pulse polarity identification or balance measurement loop to effectively suppress interference pulse signals.
● Advanced spectrum analysis processing can effectively reduce background interference.
● Multiple input channels can be used to measure the six partial discharge signals (expandable) of the test sample at one time which can easily analyze the source of the PD signal.
● Band selection gain conversion spectrum analysis and 2D and 3D graphic display are conveniently performed on the operating platform. In addition the system can print or save a single graphic and save the continuous time graphic data for analysis.
Models
Technical characteristics | |
Number of channels | 2 electrical signal interfaces one external synchronization interface |
Sampling accuracy | 12bit |
Range switching | 60Db 50dB 40dB 30dB 20dB 10dB 0dB -10dB total 8 ranges |
Frequency range | 80k-200kHz 40k-300kHz |
Nonlinear error of the range | 5% |
Measuring range | 0.1pC~100000pC |
Sensitivity | 0.1pC |
Capacitance range of the products to be tested | 6pF~250µF |
Test power frequency range | 50~400Hz |
Display | |
Display | 7” TFT true color touch LCD |
Resolution | 800×480 |
Storage | |
Physical storage | 256MB DDR2 for running memory |
SD card storage | Standard 16G card can be upgraded to 32G used to store test records and test data |
Interface | |
RS232 | RS232 used for synchronous transmission interface with PC |
USB | It can be connected to an external mouse and keyboard as well as an external mobile storage device |
Power mode | AC 220V |
Electrical signal interface | 2-way BNC interface for signal input |
SMA interface | External synchronization interface |
SD card slot | can insert SD card up to 32G |
Network port: | Can be expandable |
Grounding button | For external grounding |
General description | |
CPU | Main frequency 533MHz |
System | WINCE6.0 |
Operation temperature | -20℃ - 45℃ |
Storage temperature | -20℃ - 60℃ |
Dimension | 350mm (L)× 245mm (W)× 175mm (H) |
Weight | 5.8kg |
Input unit serial number |
Turning capacitance Ct´ |
Sensitivity Unbalanced input |
Maximum current (RMS) | |
Unbalanced input | Balance d input | |||
1 | 6pF-25pF-100pF | 0.01pc | 30mA | 0.25A |
2 | 25pF-100pF-400pF | 0.02pc | 60mA | 0.5A |
3 | 100pF-400pF-1500pF | 0.04pc | 120mA | 1A |
4 | 400pF-1500pF-6000pF | 0.08pc | 250mA | 2A |
5 | 1500pF-6000pF-0.025mF | 0.15pc | 0.5A | 4A |
6 | 6000pF-0.025mF-0.10mF | 0.3pc | 1A | 8A |
7 | 0.025mF-0.10mF-0.4mF | 0.5pc | 2A | 15A |
8 | 0.10mF-0.4mF-1.5mF | 1.0pc | 4A | 30A |
9 | 0.4mF-1.5mF-6.0mF | 1.5pc | 8A | 60A |
10 | 1.5mF-6.0mF-25mF | 2.5pc | 15A | 120A |
11 | 4.0mF-15mF-60mF | 5.0pc | 25A | 200A |
12 | 15mF-60mF-250mF | 10pc | 50A | 300A |