ZGF Series Intelligent DC Hipot Test Set is widely used in DC high voltage test of electrical equipment such as zinc oxide surge arresters, magnetic blow arresters, power cables, generators, transformers, and circuit breakers.

Overview

Product characteristics and function
● It adopts large-screen dot matrix LCD with man-machine interaction function;
● Fully automatic measurement function for zinc oxide surge arresters with good repeatability and high precision;
● Automatic test function: the test voltage can be preset and the output voltage can be maintained at a constant voltage;
● Automatic timing function: It can preset the boost time of the standard test voltage and automatically timing after the voltage rises to the standard test voltage after finishing timing it automatically drops voltage.
● The high voltage over-voltage setting is adopted with a microprocessor which has high precision and good reliability;
● Retain the manual test mode;
● Data storage function: Instantly capture test parameters and automatically save test results
● According to the theory of electromagnetic compatibility it is combined special shielding multi-stage isolation and grounding protection measures to prevent damage during discharge;
● With print function can print the test result in-time.

Models

Technical Data for the voltage lower than 400kV

       Type
Parameter
 
60/2
 
60/3
 
60/10
 
100/4
 
120/5
 
200/2
 
200/5
 
250/3
 
250/5
 
300/3
 
300/5
Output voltage (KV) 60 60 60 100 120 200 200 250 250 300 300
Output current (mA) 2 3 10 4 5 2 5 3 5 3 5
Output power (W) 120 180 600 400 600 400 1000 750 1250 900 1500
Charging current (mA) 3 4.5 15 6 7.5 3 7.5 4.5 7.5 4.5 7.5
Voltage measure accuracy  ± 1.0% (full scale) ±2digit
Current measure accuracy ± 1.0% (full scale) ±2digit
Overvoltage setting error ≤ 1%
0.75 switching error ≤ 1%
Ripple factor  ≤ 1.0%
Voltage stability Random fluctuation, it is no more than 1% when power voltage change ±10%
Way of working Intermittent use 30 minutes for rated load 10 minutes for 1.1 times rated voltage
Temperature -15 ~ 50℃
Relative humidity when the temperature is 25℃ the relative humidity should be less than 90% (non-condensing)
Altitude less than 2000m

Technical Data for the voltage higher than 400kV

       Type
Parameter
400/10 400/12 400/15 400/20 500/10 600/3 600/5
Rated output voltage (KV) 200/400 200/400 200/400 200/400 250/500 200/400/600 200/400/600
300/400 300/400 300/400 300/400 300/500 300/600 300/600
Rated current (mA) 10 12 15 20 10 3 5
Rated power (W) 4000 4800 6000 8000 5000 1800 3000
Max charging current (mA) 15 18 23 30 15 4.5 7.5
Voltage measure accuracy  ± 1.0% (full scale) ±2digit
Current measure accuracy ± 1.0% (full scale) ±2digit
Overvoltage setting error ≤ 1%
0.75 switching error ≤ 1%
Ripple factor Ripple factor ≤ 2.0% when Io≤10mA; Ripple factor ≤ 3.0% when Io≤20mA
Voltage stability Random fluctuationit is no more than 1% when power voltage change ±10%
Way of working Intermittent use 30 minutes for rated load 10 minutes for 1.1 times rated voltage
Temperature -10 ~ 40℃
Relative humidity when the temperature is 25℃ the relative humidity should be less than 85% (non-condensing)
Altitude less than 1500m
 