NRHJ Series standard potential transformer is mainly used for factory inspection of instrument transformer and used as measuring standard in metrology department. According to different voltage, it can be divided into eight types: 6kV, 10kV, 35kV, 110kV, 220kV, 500kV, 750kV, 1000kV; According to different accuracy, it can be divided into three types: 0.05%, 0.02%, 0.01%; According to whether need external high voltage, it can be divided into two types: PT with self-boost and PT without self-boost.
Overview
Models
Rated primary voltage (kV) | 6 kV | 10 kV | 35 kV | 110 kV | 220 kV |
500 kV
|
750kV
|
1000kV |
Automatic boost function |
Automatic boost / without automatic boost |
Without automatic boost | ||||||
Accuracy (%) | 0.08% 0.05% 0.02% | |||||||
Rated secondary voltage (V) | 100V 100V/root 3 | |||||||
Rated secondary capacity | 0.25VA 0.08VA 0.02VA | |||||||
Power factor | CosФ=1.0 | |||||||
Rated frequency | 50Hz | |||||||
Insulation medium | Dry type (epoxy resin) | Filled with SF6 gas | ||||||
Operating environment |
Temperature: 0℃~ 40℃
Humidity: no more than 85%
|
|||||||
Altitude |
Less than 2000 meters (High altitude can be customized)
|