The NRQH-600 SF6 gas recovery device is produced in accordance with the DL/T662-1999 "Sulfur hexafluoride charging and recovery device" standard. It is composed of SF6 compressors, vacuum pumps, vacuum systems with anti-oil return devices, condensation systems, liquid storage tanks, and purification system, built-in renewable drier filter, dust filter, ball valve, vacuum gauge, electrical control, pressure detection, thermometer and alarm device, instrument panel and other auxiliary facilities.
It is suitable for manufacturing plants of SF6 electrical appliances, GIS combined electrical appliances, SF6 gas insulated electrical equipment, operating and scientific research departments.
Overview
Product characteristics
● Vacuum pumping and vacuum measurement for SF6 switch and GIS
● Vacuum pumping and vacuum measurement of liquefaction tank
● Vacuum pumping and vacuum measurement of the device itself
● Inflate the SF6 switch
● Recover SF6 gas in electrical equipment including water treatment and oil treatment
● Dry and purify the recovered and recharged SF6 gas
● Recovery liquefaction storage and residual pressure measurement of SF6 gas in SF6 Electrical Appliances
● The equipment has a liquid storage tank with a capacity of 80 liters.
● SF6 gas is stored in compressed liquid state.
● The device is mobile
Models
Type | Freeze liquefaction vacuum water cooling movable | |
Operating temperature | -10℃~40℃ | |
Recovery | Initial pressure (Mpa) | 0.8 |
Final pressure (Mpa) | ≤ 0.05 | |
Time required for filling 1m3 volume of gas (h/m3) | ≤ 1 | |
Filling gas | Initial pressure (Pa) | ≤ 133 |
Initial pressure (Mpa) | 0.7 | |
Time required for filling 1m3 volume of gas (h/m3) | ≤ 0.3 | |
Time required for vacuum pumping from 0.1MPa to 133pa (h/m3) | ≤ 0.7 | |
Limit vacuum (Pa) | ≤ 10 | |
Purity of recovered SF6 gas (50KG) |
Moisture (PPM/V) | ≤ 60 |
Oil fraction (PPM/W) | ≤ 5 | |
Dust (um) | ≤ 1 | |
Storage container | Storage mode | gas liquid |
Pressure (MPa) | 4.0 | |
Volume (L) | 80 | |
Liquid storage capacity (kg) | 80 | |
Liquefaction method | Freezing liquefaction | |
Vaporization mode | Electric heating | |
Regeneration mode of drying filter | Vacuum heating activation regeneration | |
Power supply | Three-phase 3Φ 380V with zero line | |
Total power (kW) | ≤ 8 | |
Noise dB(A) | ≤ 75 | |
Dimension (mm) | 1400mm×1000mm×1000mm | |
Weight (kg) |
≤ 680KG
|