NRCTP-120P CT PT Analyzer is designed for analyzing current transformers (CT) and voltage transformers (PT) of protection or measurement use. Which is suitable for laboratory and on-site test. It’s a new generation of innovative CT, PT test equipment, which is based on the series of NRFA automatic instrument transformer tester, which already had a good reputation. This device uses high-performance DSP and ARM, with advanced manufacturing process to ensure stable and reliable performance, full-featured, high degree of automation, high efficiency test, it is the professional testing equipment of instrument transformer in the power industry.
Overview
NRCTP-120P CT PT Analyzer is designed for analyzing current transformers (CT) and voltage transformers (PT) of protection or measurement use. Which is suitable for laboratory and on-site test. It’s a new generation of innovative CT PT test equipment which is based on the series of NRFA automatic instrument transformer tester which already had a good reputation. This device uses high-performance DSP and ARM with advanced manufacturing process to ensure stable and reliable performance full-featured high degree of automation high efficiency test it is the professional testing equipment of instrument transformer in the power industry.
CT | PT |
VA rating (excitation) curve | VA rating (excitation) curve |
Ratio | Ratio |
Polarity | Polarity |
Secondary winding resistance | Secondary winding resistance |
Secondary load | Secondary load |
Phase (angle difference) | Phase (angle difference) |
Knee point voltage/ current | Knee point voltage/ current |
Given 5% and 10% error curve automatically | Given 5% and 10% error curve automatically |
Accuracy limit factor (ALF) | Accuracy limit factor (ALF) |
The safety factor of instrument (FS) | The safety factor of instrument (FS) |
Secondary time constant (Ts) | Secondary time constant (Ts) |
Remanence factor (Kr) | Remanence factor (Kr) |
Saturated and unsaturated inductance | Saturated and unsaturated inductance |
Models
Testing purposes | Protective CT and PT | |
Output | 0~100Vrms 12Arms 36A (peak value) | |
Voltage measuring accuracy | ±0.2% | |
CT ratio measurement |
Range | 1~10000 |
Accuracy | ±0.2% | |
PT ratio measurement |
Range | 1~10000 |
Accuracy | ±0.2% | |
Phase measurement | Accuracy | ±5min |
Resolution | 0.5min | |
Secondary winding resistance measurement | Range | 0~300Ω |
Accuracy | 2%±2mΩ | |
AC load measurement | Range | 0~300VA |
Accuracy | 2%±0.2VA | |
Input power voltage | AC220V±10%,50Hz | |
Operating Environment | Temperature: -10℃ ~ 50℃; Humidity: ≤ 90% | |
Dimension and weight | Size: 340mm × 300mm × 150mm; weight <9kg |