NRCJ series impulse voltage generator is mainly used in electric power equipment such as power transformers, transformers, combined electrical composite insulators, surge arrester and other tested objects to carry out impulse voltage test for full wave of lightning impulse voltage, chopped wave of lightning impulse voltage, operating shock wave and steep wave, testing insulation performance.
Overview
(2) Relative humidity: < 90%RH;
(3) Altitude: ≤ 1000m
(4) The maximum daily temperature difference: 25℃;
(5) The operational environment: indoor;
(6) No conductive dust;
(7) No fire and explosion hazards;
(8) No corrosive gas and insulating gases;
(9) The waveform of the power supply voltage is the actual sine wave; the waveform distortion rate is < 5%.
(2) Small circuit inductance of the impulse voltage generator a band-stop filtering measures is adopted so that a standard impulse wave is still generated even under a large capacity load and large load capacity it is applied to scientific research and business units.
(3) Large voltage utilization factor lightning wave and operating wave are not less than 90% and 80%;
(4) Compact structure beautiful appearance convenient modulated wave simple operation good synchronizing performance and reliable operation;
(5) Adopting SCR or LC constant-current charging automatic control technology which is high automation and strong anti-interference ability.
(6) Chopped wave delay is adopt the delay mode of electronic delay adjustable circuit L-C.
(7) Computer controlled to measure (fiber) system.
Models
Rated voltage (kV) |
Impulse capacitance (μF) |
Stage capacitance (μF) |
Impulse energy (kJ) |
Stage voltage (kV) |
Stage number |
Total height (mm) |
Stage height (mm) |
Weight (kg) |
±300 | 0.1625 | 0.325 | 7.31 | ±150 | 2 | 1260 | 420 | 547 |
0.25 | 0.25 | 11.25 | 611 | |||||
±450 | 0.1083 | 0.325 | 10.97 | 3 | 1680 | 420 | 694 | |
0.1666 | 0.5 | 16.87 | 758 | |||||
±600 | 0.08125 | 0.325 | 14.63 | 4 | 2100 | 420 | 842 | |
0.125 | 0.25 | 22.5 | 906 | |||||
±750 | 0.065 | 0.325 | 18.28 | 5 | 2850 | 420 | 1006 | |
0.1 | 0.5 | 28.13 | 1166 | |||||
±900 | 0.0542 | 0.325 | 21.95 | 6 | 3320 | 430 | 1186 | |
0.0833 | 0.25 | 33.74 | 1378 | |||||
±1050 | 0.0464 | 0.325 | 25.58 | 7 | 3750 | 430 | 1366 | |
0.714 | 0.5 | 39.36 | 1697 | |||||
±1200 | 0.406 | 0.325 | 29.23 | 8 | 4200 | 430 | 1545 | |
0.0625 | 0.5 | 45 | 1801 | |||||
±1350 | 0.03611/0.055 | 0.325/0.5 | 32.91/50.6 | 9 | 5200 | 430 | 1718 | |
±1500 | 0.0325/0.05 | 0.325/0.5 | 36.56/56.25 | 10 | 5700 | 430 | 1880 |