HEQG secondary voltage drop & load tester uses a large-capacity of lithium battery as the working power source, which can not only ensure the safety of the system, but also provide a relatively pure power source for the instrument, avoid power interference on-site and ensure measurement accuracy.
Overview
Models
- Temperature : -5℃ ~ 40℃
- Relative humidity : < 95% (25℃)
- Altitude: < 2500m
- Outside interference: no particularly strong vibration no particularly strong electromagnetic fields
2. The technical specifications when secondary voltage drop test
(1) Measuring range:
Ratio error: 0.001% ~ 19.99%; Angle error: 0.01’ ~ 599’
(2) Resolution:
Ratio error: 0.001%; Angle error: 0.01’
(3) The instrument error
-DX=± (1%×X+1%×Y±2 digits);
-DY=± (1%×X+1%×Y±2 digits).
2 Digit means the quantization error of the instrument.
(4) The accuracy of voltage meter: 0.5%
(5) Working range
- Voltage: (50 ~ 120) V
(6) The instrument indicates action value (Error prompt)
- Error prompt: when ratio error is more than 20% or angle error is more than 600’.
- Voltage prompt: when voltage is less than 2V.
3. The technical specifications when PT secondary load test
1) PT secondary load test
Admittance measuring range: 0.1ms ~ 50.0ms
Measurement accuracy of admittance:
- Secondary voltage: 50V~ 120V
- ∆X = ± ( X*1%+Y *1% ±2 digits )
- ∆Y = ± ( X*1%+Y *1% ±2 digits )
Note: when the measured values is less than 0.2mS the test voltage shall be maintained at 50V or more while paying attention to the feedthrough wire clamp remain in center. The quantization error of instrument is 5 digits.
2) The accuracy of voltage meter: 0.5%
4. The technical specifications when CT secondary load test
1) CT secondary load test
- Impedance measurement range: 0.1Ω ~ 50.0Ω
- Impedance measurement accuracy:
- ∆X = ± ( X*1%+Y *1% ±2 digits )
- ∆Y = ± ( X*1%+Y *1% ±2 digits )
2) The accuracy of current meter: 1%
2 Digit means the quantization error of the instrument.