NRYZ-2008 Transformer Load Tap Changer Tester is an integrated measuring instrument for measuring and analyzing the electrical performance indicators of on-load tap-changers of power transformers and special transformers. It adopts microcomputer control, through the design of precision measurement circuit, it can realize accurate measurement of the on-load tap-changer's transition time, transition waveform, transition resistance, three identical phases and other parameters.
The instrument has the functions of displaying, analyzing, storing and printing the measured data. It can diagnose the potential fault of the load tap switch in the preventive test of the power equipment and the maintenance of the transformer.
Overview
● Data analysis humanized can identify the trouble among the waveform automatically and making marks\;
● Waveform display is based on data back to automatically adjust the sampling time and the magnitude of the resistance;
● Can test with winding or without.
● Four-terminal connect wire method provide high-precision resistance to measure without wire compensation;
● Can test continuously in the process of be testing saving transformer outage time;
● Instrument can generate word report to facilitate data management and query;
● It is controlled by a small computer with a 800*480 color LCD touch screen high-speed thermal printer support for external keyboard and mouse easy to operate;
● Instrument's internal can save 800 sets of data automatically or can be saved by U disk.
- NRYZ-2008 Transformer Load Tap Changer Tester 1 piece
- 10 meters of test line with test clamp 4 pieces
- 1 meter test line with alligator clip 4 pieces
- Power wire 1 piece
- SD memory card 1 piece
- Card reader 1 piece
- Disc 1 piece
- Printing paper 2 rolls
- Operational manual 1 copy
- Factory inspection report 1 copy
Models
Voltage output | > 20V |
Current output | ≥ 1A |
Power supply | AC220V±10% 50Hz |
Power | 180W |
Resistance measuring range | 0.3 ~ 50Ω |
Resistance measuring accuracy |
0.1Ω ~ 1Ω ± 0.1Ω; 1Ω ~ 50Ω ±5% ( do not include 1Ω ) |
Time measuring range | 1 ms ~ 256 ms |
Time measuring accuracy |
1 ms ~ 100 ms ± 0.1ms; 100 ms ~ 250ms ± 1% |
Three-phase synchronism | 0.1 ms |
Sampling frequency | 10 ~ 20KHz |
Operating temperature | 0 ~ 40℃ |
Relative humidity | ≤ 80%RH |
Dimensions | 420mm×350mm×220m |
Weight | 12kg (including accessories) |