NRJS-3 Series dielectric loss tester calibrator is mainly used to calibrate dielectric loss tester. It has been widely used as insulation testing instrument of power equipment. Due to its high stability and high accuracy (absolute value), the calibrator has been widely used. Therefore, it is a very convenient calibration instrument for both laboratory and field operations.
Overview
(2) Simple operation and efficient work;
(3) The dielectric loss tester calibrator adopts the principle of simulating loss the power consumption of the loss device itself is very small and it can realize the simulation of any dielectric loss value. With the high-performance single-chip microcomputer it can realize infrared remote control switching;
(4) It can also be used for reverse wiring measurement.
Models
(1) Ambient temperature: 20℃±5℃;
(2) Relative humidity: RH < 85%;
(3) Rated voltage: 10kV;
(4) Rated frequency: 50Hz; 8×10-3
(5) Electric capacity: 1000pF; (subject to the measured capacitance)
(6) Accuracy: tgδ: 0.5% of reading ± 0.01%
Cx: 0.5% of reading ±0.1pF
(7) Nominal value of loss factor: 0 1×10-4 2×10-4 3×10-4 4×10-4 5×10-4 6×10-4 7×10-4 8 ×10-4 9×10-4 1×10-3 2×10-3 3×10-3 4×10-3 5×10-3 6×10-3 7×10 -3 8×10-3 9×10-3 1×10-2 2×10-2 3×10-2 4×10-2 5×10-2 6×10-2 7×10-2 8×10-2 9×10-2 1×10-1 (total 30 levels)
(8) The dielectric loss range of 100pF and 1000pF is 0~1×10-1; the dielectric loss range of 10000pF is 0~1×10-2 the specific gear setting can be customized according to user requirements
(9) The stable value of the capacitance value (subject to the actual measured value): ±0.1%
(10) The maximum allowable error of the dielectric loss factor (subject to the actual measured value): ±0.5%±1×10-4