The capacitance & inductance tester for capacitor is specially developed for the existing problems when measuring the capacitance value of a single capacitor in a shunt capacitor bank in the substation field. It focuses on solving the following problems:
	(1) To measure a single capacitor on site, the connecting wire needs to be removed, which not only requires a lot of work, but also easily damages the capacitor.
	(2) The low output voltage of the capacitance meter leads to a low failure detection rate.
	(3) Measure the inductance of the reactor.
    Overview
	Product introduction
	 
	The capacitance & inductance tester for capacitor is specially developed for the existing problems when measuring the capacitance value of a single capacitor in a shunt capacitor bank in the substation field. It focuses on solving the following problems:
	(1) To measure a single capacitor on site the connecting wire needs to be removed which not only requires a lot of work but also easily damages the capacitor.
	(2) The low output voltage of the capacitance meter leads to a low failure detection rate.
	(3) Measure the inductance of the reactor.
	Functions and characters
	 
	(1) Automatic range conversion;
	(2) Can store 7168 test data;
	(3) Large-screen LCD (320×240 LCD) display menus with operation prompts;
	(4) The waveform and measurement processing data are displayed on the same screen making the test process more intuitive;
	(5) It has the functions of setting correcting and debugging.
Models
| Capacitance measurement range | Capacitance measurement range: 0.2μF ~ 2000μF | 
| Capacitance range: 5 ~ 20000kvar | |
| Measurement accuracy: 0.2μF ~ 2μF ±1% of reading ±0.02μF; 2μF ~ 2000μF ±1% of reading ±2 digits. | |
| Inductance measurement range | Inductance measurement range: 1mH ~ 9.99H; | 
| Measurement accuracy: ±1.5% of reading ±2 digits; | |
| Output measurement voltage | AC 26V/500VA 50Hz | 
| Display mode | large-screen LCD display TPμp-40 panel thermal printer | 
| Dimension | 370mm×370mm×220mm | 
| Weight | around 16kg | 
| Working conditions: | a. Temperature: 0℃ ~ +40℃ relative humidity: ≤90% b. Power source: AC 220V±10%; 50Hz; | 



 
 
 

 
 
 
 
 
 
 