Transformer DC Resistance Tester also named Transformer Winding Resistance Tester, It is a necessary testing project for transformer transition, overhauling and changing tap switch, it is also an important detecting project after fault. Transformer DC Resistance Tester is a quick test equipment for testing transformers, generators, motors, lines and other DC resistance.
Overview
1. Large output current wide measuring range small size light weight simple operation;
2.Fast test speed,high measurement accuracy,good retest capacity,strong anti-interference capability;
3. With perfect function of protection circuit and discharge alarm reduce the wrong operation good reliability;
4. Adopting high speed micro-controller to automatically complete the judgment of steady flow data acquisition and processing and display resistance;
5. Using 192 * 64 large-screen LCD display outdoor display is clearly visible;
6. Built-in high-capacity a non-volatile memory can store 500 sets of measurement data;
7. Built-in high-precision real-time clock function date and time can be calibrated.
8. With high-speed micro thermal printer: can print measurement and historical data.
Models
Item | NRZDC Low Resistance Ohmmeter (5A-10A) | |||
NRZDC-5A | NRZDC-10A | |||
Testing current | 5A 2A 1A 100mA 10mA 1mA | 10A 5A 1A 100mA 10mA 1mA | ||
Testing range | 5A | 1mΩ~4Ω | 10A | 500μΩ~2Ω |
2A | 5mΩ~10Ω | 5A | 1mΩ~4Ω | |
1A | 10mΩ~20Ω | 1A | 10mΩ~20Ω | |
100mA | 1Ω~200Ω | 100mA | 1Ω~200Ω | |
10mA | 10Ω~2kΩ | 10mA | 10Ω~2kΩ | |
1mA | 100Ω~20kΩ | 1mA | 100Ω~20kΩ | |
Measurement accuracy | ±0.2% (full scale) ±2digit | |||
Data storage | 500 | |||
Display | 192*64 Large screen LCD | |||
Resolution ratio | 0.1μΩ | |||
Power supply |
AC220V±10%50Hz±1Hz (protective tube 5A) |
|||
Environment temperature | -10℃~50℃ | |||
Relative humidity | ≤85%RH | |||
Dimension | 320mm×250mm×180mm | |||
Weight | 9.4kg (Including Test clamp and test line) |